ASHRAE-90.1-2022- - Page 366

Extracted Content

Table J-5 Chiller Performance Curves for Section 12 (Simulation Input Required in SI Units) (Continued)

SetDescriptionOutput
Variable
Coeff 1Coeff 2Coeff 3Coeff 4Coeff 5Coeff 6
GLiquid-cooled positive
displacement ≥600
tons 0.560 FL, 0.500
IPLV.IP Path A
EIR-f-T0.544967–0.0304910.0013950.027852–0.000187–0.000314
GLiquid-cooled positive
displacement ≥600
tons 0.560 FL, 0.500
IPLV.IP Path A
CAP-f-T0.8308040.016310–0.0009490.008707–0.0002630.000377
GLiquid-cooled positive
displacement ≥600
tons 0.560 FL, 0.500
IPLV.IP Path A
EIR-f-PLR0.2643710.2633020.471690
HLiquid-cooled
centrifugal <150 tons
0.610 FL, 0.550
IPLV.IP Path A
EIR-f-T0.447243–0.0337850.0007240.040274–0.0005770.000305
HLiquid-cooled
centrifugal ≥150 tons
<300 tons 0.610 FL,
0.550_IPLV_.IP Path A
CAP-f-T0.8374200.038528–0.0021670.004185–0.0003220.000806
HLiquid-cooled
centrifugal ≥150 tons
<300 tons 0.610 FL,
0.550_IPLV_.IP Path A
EIR-f-PLR0.3042060.0738660.621457
ILiquid-cooled
centrifugal ≥300 tons
<400 tons 0.560 FL,
0.520_IPLV_.IP Path A
EIR-f-T0.647193–0.0244840.0004260.028764–0.0004210.000077
ILiquid-cooled
centrifugal ≥300 tons
<400 tons 0.560 FL,
0.520_IPLV_.IP Path A
CAP-f-T1.2078780.026951–0.001148–0.0205760.0002020.000479
ILiquid-cooled
centrifugal ≥300 tons
<400 tons 0.560 FL,
0.520_IPLV_.IP Path A
EIR-f-PLR0.2769610.1017490.621383
JLiquid-cooled
centrifugal ≥400 tons
<600 tons 0.560 FL,
0.500_IPLV_.IP Path A
EIR-f-T0.489242–0.0288510.0009730.035835–0.0004770.000096
JLiquid-cooled
centrifugal ≥600 tons
0.560 FL, 0.500
IPLV.IP Path A
CAP-f-T0.8968060.056739–0.002544–0.005536–0.0001050.000470
JLiquid-cooled
centrifugal ≥600 tons
0.560 FL, 0.500
IPLV.IP Path A
EIR-f-PLR0.2908910.0593660.649421
KAir-cooled <150 tons,
9.700 FL, 15.800
IPLV.IP Path B
EIR-f-T0.891872–0.0298210.001459–0.0069290.000453–0.000303
KAir-cooled <150 tons,
9.700 FL, 15.800
IPLV.IP Path B
CAP-f-T0.7091950.059566–0.0019680.010899–0.000284–0.000222
KAir-cooled <150 tons,
9.700 FL, 15.800
IPLV.IP Path B
EIR-f-PLR0.0368490.1007921.614142–0.748013
LAir-cooled ≥150 tons,
9.700 FL, 16.100
IPLV.IP Path B
EIR-f-T0.711589–0.0295200.0013900.0015540.000353–0.000272
LAir-cooled ≥150 tons,
9.700 FL, 16.100
IPLV.IP Path B
CAP-f-T0.8798440.060415–0.0019940.000937–0.000156–0.000155
LAir-cooled ≥150 tons,
9.700 FL, 16.100
IPLV.IP Path B
EIR-f-PLR0.0957110.0099031.543396–0.646737
MLiquid-cooled positive
displacement <75 tons
0.780 FL, 0.500
IPLV.IP Path B
EIR-f-T0.844064–0.0325040.001571–0.0030760.000545–0.000402
MLiquid-cooled positive
displacement <75 tons
0.780 FL, 0.500
IPLV.IP Path B
CAP-f-T0.8358030.057057–0.0021190.000903–0.0001760.000019
MLiquid-cooled positive
displacement <75 tons
0.780 FL, 0.500
IPLV.IP Path B
EIR-f-PLR0.1072000.1826110.705182
NLiquid-cooled positive
displacement ≥75 and
<150 tons 0.750 FL,
0.490_IPLV_.IP Path B
EIR-f-T0.797371–0.0313610.0015140.0004190.000473–0.000398
NLiquid-cooled positive
displacement ≥75 and
<150 tons 0.750 FL,
0.490_IPLV_.IP Path B
CAP-f-T0.8507100.056037–0.002077–0.000147–0.0001530.000023
NLiquid-cooled positive
displacement ≥75 and
<150 tons 0.750 FL,
0.490_IPLV_.IP Path B
EIR-f-PLR0.183811–0.0444170.855660
OLiquid-cooled positive
displacement ≥150 and
<300 tons 0.680 FL,
0.440_IPLV_.IP Path B
EIR-f-T0.617871–0.0201100.0011750.0136230.000172–0.000439
OLiquid-cooled positive
displacement ≥150 and
<300 tons 0.680 FL,
0.440_IPLV_.IP Path B
CAP-f-T0.8225190.038968–0.0015880.004048–0.0001880.000164
OLiquid-cooled positive
displacement ≥150 and
<300 tons 0.680 FL,
0.440_IPLV_.IP Path B
EIR-f-PLR0.0909360.2078120.696735
PLiquid-cooled positive
displacement ≥300 and
<600 tons 0.625 FL,
0.410_IPLV_.IP Path B
EIR-f-T0.656763–0.0278910.0013430.0166270.000056–0.000348
PLiquid-cooled positive
displacement ≥300 and
<600 tons 0.625 FL,
0.410_IPLV_.IP Path B
CAP-f-T0.8772180.028393–0.0012570.003217–0.0001740.000232
PLiquid-cooled positive
displacement ≥300 and
<600 tons 0.625 FL,
0.410_IPLV_.IP Path B
EIR-f-PLR0.1036650.1480240.744887

364 ANSI/ASHRAE/IES Standard 90.1-2022 (I-P)