Table L2.2.3 Proposed Building HVAC System Parameters (Continued)

CategoryParameterFixed or User
Defined
RequiredApplicable
Systems a
System Fan
Power
and Controls
Design fan power, W/cfmUser definedInput electric power for all fans required to operate at_fan system design conditions_
divided by the supply airflow rate. Include any VSD losses at design condition. This
is a wire-to-air value, including all drive, motor_efficiency_, and other losses.
All
System Fan
Power
and Controls
Part-load fan controls:
• Constant volume
• Two-speed or three-speed, then input:
• W/cfm at each speed
• % cfm at leach speed
• VAV
User definedStatic pressure_reset_ included for_VAV_All (constant
volume, two speed)
9, 10, 11 (VAV)
Variable-Air-
Volume Systems
SAT controls (select):
• None
• OAT SAT_reset_
• Warmest zone SAT_reset_
User definedIf not SAT_reset_, then constant at 55°F. Options for_reset_ based on OAT or warmest
zone. If OAT_reset_, SAT is_reset_ higher to 60°F at outdoor low of 50°F. SAT is 55°F
at outdoor high of 70°F. If warmest zone, then the user can specify the minimum and
maximum temperatures.
9, 10, 11
Variable-Air-
Volume Systems
• Zone minimum damper and_Evs_
• Standard 62.1 simple method except for schools
Fixed• Schools: 1.2 ×Voz zone minimum design_ventilation_ rate, cfm;Evs = 0.65
• Other_buildings_: Simple Standard 62.1 method is 1.5 ×Voz zone minimum design
ventilation rate, cfm;Evs = 0.75.
9, 10, 11
Variable-Air-
Volume Systems
Dual_set point_ minimum_VAV_ damper positionUser definedHeating minimum and maximum airflow fraction9, 10, 11
Variable-Air-
Volume Systems
Terminal-unit heating sourceUser definedElectric or hydronic
Variable-Air-
Volume Systems
FPTU typeUser definedSeries or parallel FPTU11
Variable-Air-
Volume Systems
Parallel FPTU fanSized for 50% peak primary air at 0.35 W/cfm11
Variable-Air-
Volume Systems
Series FPTU fanFixedSized for 50% peak primary air at 0.35 W/cfm11
EconomizerOSA economizer presenceUser definedYes or no3, 4, 5, 6, 9, 10, 11
EconomizerEconomizer high limitFixed• Lockout on differential dry-bulb temperature (OAT > RAT) in Climate Zones 6A,
5A, All B, and C
• Fixed enthalpy > 28 Btu/lb or fixed dry-bulb OAT > 75°F in Climate Zones 0A to
4A
Energy
Recovery
Sensible effectivenessUser definedHeat exchanger sensible effectiveness at design heating and cooling conditions3, 4, 9, 10, 11, 12
Energy
Recovery
Latent effectivenessUser definedHeat exchanger latent effectiveness at design heating and cooling conditions3, 4, 9, 10, 11, 12
Energy
Recovery
Bypass SAT_set point_User definedIf bypass, target supply air temperature3, 4, 9, 10, 11, 12
Energy
Recovery
Fan power reduction when in bypassUser definedIf bypass, specify fan power reduction, W/cfm.3, 4, 9, 10, 11, 12

a. Applicable systems from Table L.1.1.1 Informative Note: See Section 3.3 for a full list of terms used in this table.