Table L2.2.3 Proposed Building HVAC System Parameters (Continued)

CategoryParameterFixed or User
Defined
RequiredApplicable
Systems a
Condenser
Loop
Condenser water-pump power, W/gpmUser definedPump input, W/gpm; condenser water flow6, 7, 8, 10, 11, 12
Condenser
Loop
Condenser water-pump controlFixedConstant-speed, one_pump_ per chiller6, 7, 8, 10, 11, 12
Heat RejectionHeat-rejection_equipment efficiency_User definedgpm/hp at_design conditions_, where hp is the sum of nameplate fan and integral
spray_pump_ motor hp, if applicable
6, 7, 8, 10, 11, 12
Heat RejectionOpen-circuit cooling tower flow turndownFixedFlow turndown per Section 6.5.5.46, 7, 8, 10, 11, 12
Heat RejectionHeat-rejection fan controlUser definedConstant or variable speed6, 7, 8, 10, 11, 12
Heat RejectionHeat-rejection approach and rangeUser definedDesign heat-rejection approach and range temperature6, 7, 8, 10, 11, 12
Heat-Pump
Loop
Loop flow and heat-pump control valveFixedTwo-position valve with VSD on_pump_7, 8
Heat-Pump
Loop
Heat-pump loop flow controlFixedLoop flow at 3 gpm/ton7, 8
Heat-Pump
Loop
Heat-pump loop minimum and maximum
temperature control
User definedUser input; restrict to minimum 20°F and maximum 40°F temperature difference.7, 8
Ground-Loop
Heat-Pump
Bore Field
FixedBore depth = 250 ft; bore length 200 ft/ton for greater of cooling or heating load8
Ground-Loop
Heat-Pump
Bore Field
FixedBore spacing = 15 ftBore spacing = 15 ft
Ground-Loop
Heat-Pump
Bore Field
FixedBore diameter = 5 in. with 3/4 in. nominal diameter polyethylene pipeBore diameter = 5 in. with 3/4 in. nominal diameter polyethylene pipe
Ground-Loop
Heat-Pump
Bore Field
FixedGround and grout conductivity = 4.8 Btu·in./h·ft2·°FGround and grout conductivity = 4.8 Btu·in./h·ft2·°F

a. Applicable systems from Table L.1.1.1 Informative Note: See Section 3.3 for a full list of terms used in this table.