Table L2.2.3 Proposed Building HVAC System Parameters (Continued)
| Category | Parameter | Fixed or User Defined | Required | Applicable Systems a |
|---|---|---|---|---|
| Condenser Loop | Condenser water-pump power, W/gpm | User defined | Pump input, W/gpm; condenser water flow | 6, 7, 8, 10, 11, 12 |
| Condenser Loop | Condenser water-pump control | Fixed | Constant-speed, one_pump_ per chiller | 6, 7, 8, 10, 11, 12 |
| Heat Rejection | Heat-rejection_equipment efficiency_ | User defined | gpm/hp at_design conditions_, where hp is the sum of nameplate fan and integral spray_pump_ motor hp, if applicable | 6, 7, 8, 10, 11, 12 |
| Heat Rejection | Open-circuit cooling tower flow turndown | Fixed | Flow turndown per Section 6.5.5.4 | 6, 7, 8, 10, 11, 12 |
| Heat Rejection | Heat-rejection fan control | User defined | Constant or variable speed | 6, 7, 8, 10, 11, 12 |
| Heat Rejection | Heat-rejection approach and range | User defined | Design heat-rejection approach and range temperature | 6, 7, 8, 10, 11, 12 |
| Heat-Pump Loop | Loop flow and heat-pump control valve | Fixed | Two-position valve with VSD on_pump_ | 7, 8 |
| Heat-Pump Loop | Heat-pump loop flow control | Fixed | Loop flow at 3 gpm/ton | 7, 8 |
| Heat-Pump Loop | Heat-pump loop minimum and maximum temperature control | User defined | User input; restrict to minimum 20°F and maximum 40°F temperature difference. | 7, 8 |
| Ground-Loop Heat-Pump Bore Field | Fixed | Bore depth = 250 ft; bore length 200 ft/ton for greater of cooling or heating load | 8 | |
| Ground-Loop Heat-Pump Bore Field | Fixed | Bore spacing = 15 ft | Bore spacing = 15 ft | |
| Ground-Loop Heat-Pump Bore Field | Fixed | Bore diameter = 5 in. with 3/4 in. nominal diameter polyethylene pipe | Bore diameter = 5 in. with 3/4 in. nominal diameter polyethylene pipe | |
| Ground-Loop Heat-Pump Bore Field | Fixed | Ground and grout conductivity = 4.8 Btu·in./h·ft2·°F | Ground and grout conductivity = 4.8 Btu·in./h·ft2·°F |
a. Applicable systems from Table L.1.1.1 Informative Note: See Section 3.3 for a full list of terms used in this table.