Table L4.3.2-1 TSPR Reference Building Design HVAC Complex Systems

Building Type ParameterLarge Office (warm) aLarge Office (cold) bSchool (warm) aSchool (cold) b
System typeVAV/reheat
water-cooled chiller/
electric_reheat_ with parallel fan
powered boxes
VAV/reheat
water-cooled chiller/
gas_boiler_
VAV/reheat
water-cooled chiller/
electric_reheat_ with parallel fan
powered boxes
VAV/reheat
water-cooled chiller/
gas_boiler_
Fan controlVSD, no static pressure_reset_VSD, no static pressure_reset_VSD, no static pressure_reset_VSD, no static pressure_reset_
Main fan power (W/cfm) proposed ≥MERV131.1651.1651.1651.165
Main fan power (W/cfm) proposed <MERV131.0661.0661.0661.066
Zonal fan power, W/cfm0.35NA0.35NA
Minimum zone airflow fraction1.5 ×Voz1.5 ×Voz1.2 ×Voz1.2 ×Voz
Heat/cool sizing factor1.25/1.151.25/1.151.25/1.151.25/1.15
Outdoor air economizerNoYes except 4ANoYes except 4A
Occupied_outdoor air_ (= proposed)Sum(Voz)/0.75Sum(Voz)/0.75Sum(Voz)/0.65Sum(Voz)/0.65
Energy recovery ventilator_enthalpy recovery_
ratio bypass; SAT set point
NANA50%; no bypass50%; 60°F except no bypass
required in Climate Zone 4A
Demand control ventilationNoNoNoNo
Cooling source2 water-cooled centrif. chillers2 water-cooled centrif. chillers2 water-cooled screw chillers2 water-cooled screw chillers
Cooling_efficiency_Table G3.5.3Table G3.5.3Table G3.5.3Table G3.5.3
Heating source (reheat)Electric resistanceGas_boiler_Electric resistanceGas_boiler_
Furnace or_boiler_ efficiency1.075%Et1.080%Et
Condenser heat rejectionAxial-fan open-circuit cooling towerAxial-fan open-circuit cooling towerAxial-fan open-circuit cooling towerAxial-fan open-circuit cooling tower
Cooling-tower_efficiency_, gpm/hp
(See Section G3.2.3.11)
38.238.238.238.2
Open-circuit cooling-tower turndown (>300 ton)50%50%50%50%
Pump (constant flow/variable flow)Constant flow; 10°F rangeConstant flow; 10°F rangeConstant flow; 10°F rangeConstant flow; 10°F range
Open-circuit cooling-tower approachG3.1.3.11G3.1.3.11G3.1.3.11G3.1.3.11
Cooling condenser_pump_ power, W/gpm19191919

a. “Warm” refers to Climate Zones 0 through 2 and 3A. b. “Cold” refers to Climate Zones 3B, 3C, and 4 through 8. Informative Note: See Section 3.3 for a full list of terms used in this table.