ASHRAE-90.1-2022- - Page 391

Extracted Content

Table L4.3.2-2 TSPR Reference Building Design HVAC Simple Systems 1

Building Type
Parameter
Medium Office
(warm)a
Medium Office
(cold) b
Small Office
(warm) a
Small Office
(cold) b
Retail
(warm) a
Retail
(cold) b
System typePackage_VAV_—
electric_reheat_
Package_VAV_—
hydronic_reheat_
PSZ-HPPSZ-ACPSZ-HPPSZ-AC
Fan controlVSD, no static
pressure reset
VSD, no static
pressure reset
Constant volumeConstant volumeConstant volumeConstant volume
Main fan power (W/cfm) proposed
≥MERV13
1.2851.2850.9160.9160.8990.899
Main fan power (W/cfm) proposed
<MERV13
1.1761.1760.8500.8500.8350.835
Zonal fan power (W/cfm)0.35NANANANANA
Minimum zone airflow fraction30%30%NANANANA
Heat/cool sizing factor1.25/1.151.25/1.151.25/1.151.25/1.151.25/1.151.25/1.15
Supplemental heating availabilityNANA<40°F OATNA<40°F OATNA
Outdoor air economizerNoYes except 4ANoYes except 4ANoYes except 4A
Occupied_outdoor air_sourcePackaged unit, occupied damper, all_building_ use typesPackaged unit, occupied damper, all_building_ use typesPackaged unit, occupied damper, all_building_ use typesPackaged unit, occupied damper, all_building_ use typesPackaged unit, occupied damper, all_building_ use typesPackaged unit, occupied damper, all_building_ use types
Energy recovery ventilatorNoNoNoNoNoNo
Demand control ventilationNoNoNoNoNoNo
Cooling sourceDX, multistageDX, multistageDX, single stage
(heat pump)
DX, single stageDX, single stage
(heat pump)
DX, single stage
Cooling_COP_ (net of fan)3.403.403.003.003.403.50
Heating sourceElectric resistanceGas_boiler_Heat pumpFurnaceHeat pumpFurnace
Heating_COP_ (net of fan)/furnace
or_boiler_ efficiency
1.075%Et3.4080%Et3.4080%Et

a. “Warm” refers to Climate Zones 0 through 2 and 3A. b. “Cold” refers to Climate Zones 3B, 3C, and 4 through 8. Informative Note: See Section 3.3 for a full list of terms used in this table.