Table L4.3.2-3 TSPR Reference Building Design HVAC Simple Systems 2

Building Type
Parameter
Hotel
(warm) a
Hotel
(cold) b
Multifamily
(warm) a
Multifamily
(cold) b
System typePTHPPTACPTHPPTAC
Fan controlConstant volumeConstant volumeConstant volumeConstant volume
Main fan power, W/cfm0.3000.3000.3000.300
Heat/cool sizing factor1.25/1.151.25/1.151.25/1.151.25/1.15
Supplemental heating availability<40°FNA<40°FNA
Outdoor air economizerNoNoNoNo
Occupied_outdoor air_ sourcePackaged unit, occupied damperPackaged unit, occupied damperPackaged unit, occupied damperPackaged unit, occupied damper
Energy recovery ventilatorNoNoNoNo
Demand control ventilationNoNoNoNo
Cooling sourceDX, single stage (heat pump)DX, single stageDX, single stage (heat pump)DX, single stage
Cooling_COP_ (net of fan)3.103.203.103.20
Heating sourcePTHP2 hydronic_boilers_PTHP2 hydronic_boilers_
Heating_COP_ (net of fan)/furnace
or_boiler_ efficiency
3.1075%Et3.1075%Et
Heating_pump_ power, W/gpmNA19NA19
Heating-coil HW temperature difference,FNA50NA50
Design HWST,FNA180NA180
HWST reset_set point_ vs. OAT,FNAHWST/OAT: 180–150/20–50NAHWST/OAT: 180–150/20–50
HW-loop pumping controlNATwo-way valves and ride_pump_
curve
NATwo-way valves and ride_pump_
curve

a. “Warm” refers to Climate Zones 0 through 2 and 3A. b. “Cold” refers to Climate Zones 3B, 3C, and 4 through 8. Informative Note: See Section 3.3 for a full list of terms used in this table.