ASHRAE-90.1-2022- - Page 395

Extracted Content

(This appendix is not part of this standard. It is merely informative and does not contain requirements necessary for conformance to the standard. It has not been processed according to the ANSI requirements for a standard and may contain material that has not been sub- ject to public review or a consensus process. Unresolved objectors on informative material are not offered the right to appeal at ASHRAE or ANSI.)

INFORMATIVE APPENDIX M ADDENDA DESCRIPTION

ANSI/ASHRAE/IES Standard 90.1-2022 incorporates all addenda to ANSI/ASHRAE/IES Standard 90.1-2019. Table M-1 lists each addendum and describes the way in which the standard is affected by the change. It also lists the ASHRAE, IES, and ANSI approval dates for each addendum.

Table M-1 Addenda to ANSI/ASHRAE/IES Standard 90.1-2019

AddendumSectionsDescription of ChangesaASHRAE
Standard
Committee
Approval
Cosponsor
Approval
(IES)
ASHRAE
BOD/Tech
Council
Approval
ANSI
Approval
afG3.1, G3.6Modifies lighting modeling requirements in Appendix G with more specific guidance on determining lighting power in
the baseline vs. proposed building.
6/30/20205/29/2020N/A6/30/2020
bc6.5.4.8Requires condensing boilers for new construction to achieve condensing-level efficiency (i.e., 90%Et) for large boiler
systems (i.e., between 1 and 10 million Btuh) and, to ensure condensing occurs, requires boiler entering water to be in
the prescribed limits for temperature or flow rate.
6/30/20205/29/2020N/A6/30/2020
cd6.5.6.1.2Establishes a minimum enthalpy recovery ratio for energy recovery systems and specifies how bypass or control of the
energy recovery system must operate to ensure proper economizer performance.
6/30/20205/29/2020N/A6/30/2020
dbG3.1, G3.4-9Clarifies how to establish the Normative Appendix G baseline space conditioning categories that must be used in
conjunction with Tables G3.4-1 through G3.4-8 so that the baseline envelope will remain consistent should Section 3
undergo changes.
6/30/20205/29/2020N/A6/30/2020
by3.2, 10.2.1, 10.5.1Adds a minimum prescriptive requirement for on-site renewable energy.6/26/20205/19/20207/1/20207/31/2020
ck12.4.1, 12.4.3,
Table 12.5.1
Explains Section 12 modeling requirements for proposed designs that utilize a trade-off for the renewable energy
requirements in Section 10.5.1.
6/26/20205/19/20207/1/20207/31/2020
cp4.2.1.1, G2.2, Table G3.1Explains Appendix G modeling requirements for proposed designs that utilize a trade-off for the renewable energy
requirements in Section 10.5.1.
6/26/20205/19/20207/1/20207/31/2020
a6.5.3.7, 6.5.3.8, 13Establishes minimum fan efficacy requirements for low-power ventilation fans and references Standard 62.2 for
determining the minimum ventilation rates for nontransient dwelling units.
10/30/202010/7/2020N/A10/30/2020
b6.4.3.8Revises demand control ventilation parameters to be based on climate zone and Standard 62.1 airflow requirements.10/30/202010/7/2020N/A10/30/2020
c6.3.2, 6.4.3.3Requires residential HVAC systems greater than 2.1 kW to be equipped with start/stop and setback controls.10/30/202010/6/2020N/A10/30/2020
d3.2, 6.4.3.4.5Adds new term to define parking garage section so that fan requirements can be refined for different configurations.
Requires fans with the ability to modulate airflow and power as specified.
12/30/202012/16/2020N/A12/30/2020
fTable 6.5.1-2Clarifies the efficiency improvement required in order to eliminate an economizer.2/26/20212/18/2021N/A2/26/2021
g6.5.1.1.5Adds more specific language about relieving excess outdoor air during air economizer operation through the use of fans
or dampers.
12/30/202012/16/2020N/A12/30/2020
a. These descriptions may not be complete and are provided for information only.a. These descriptions may not be complete and are provided for information only.a. These descriptions may not be complete and are provided for information only.a. These descriptions may not be complete and are provided for information only.a. These descriptions may not be complete and are provided for information only.a. These descriptions may not be complete and are provided for information only.a. These descriptions may not be complete and are provided for information only.