Table M-1 Addenda to ANSI/ASHRAE/IES Standard 90.1-2019 (Continued)

AddendumSectionsDescription of ChangesaASHRAE
Standard
Committee
Approval
Cosponsor
Approval
(IES)
ASHRAE
BOD/Tech
Council
Approval
ANSI
Approval
bk6.3.2, 6.4.3.3.2, 6.4.3.3.5,
6.4.5, 6.4.6, 12.4.1.1,
12.5.2, G2.2.1
Updates humidity control requirements in accordance with the latest Standard 62.1-2019.1/21/20221/18/2022N/A1/21/2022
bm6.5.3.8Modifies occupied-standby controls from multiple-zone systems to explicitly require an outdoor air reset when
ventilation is reduced to zero.
1/21/20221/18/2022N/A1/21/2022
bp9.4.1.3Removes the exception for captive card key controls in hotel guestrooms9/30/20229/8/2022N/A9/30/2022
bq8.4.3Adds a requirement to perform electrical energy monitoring with separate metering for refrigeration systems where
refrigeration accounts for 10% or more of the building load.
6/25/20226/17/20226/29/20227/29/2022
br9.4.3Increases the efficacy threshold for lamps and luminaires in dwelling units and specifies requirements for interior and
exterior lighting controls.
6/25/20226/17/20226/29/20227/29/2022
bs9.3.1, 9.3.2Updates the lighting power allowances (LPA) in the Simplified Building Method Compliance Path to maintain
alignment with the established method (0.9x the Building Area Method LPA values.). Removes an exception for
alterations that had incentivized the use of LEDs before they became commonplace.
7/29/20227/26/2022N/A7/29/2022
btG3.1.3.5, G3.1.3.10,
G3.1.3.19
Indicates that baseline system pumps are to be modeled based on the presence of a load and preheat coil temperature is
to be modeled compared to the zone with the highest set point.
6/30/20226/10/2022N/A6/30/2022
bvTable 4.2.1.1Updates the building performance factors (BPFs) used to determine compliance with Normative Appendix G based on
energy-efficiency improvements in the 2022 standard.
6/30/20226/10/2022N/A6/30/2022
bw6.5.3.1.3Clarifies that the fan efficiency metric is to be applied at the highest design airflow rate.4/29/20224/27/2022N/A4/29/2022
bxTable 6.8.1-5Modifies Table 6.8.1-5 for warm air furnace efficiency requirements to more accurately distinguish between different
products and test procedures based on locations in which they are used and their status as DOE or non-DOE covered
products.
7/29/20227/26/2022N/A7/29/2022
bz6.5.6Adds language to specify the sensible energy recovery ratio requirement for systems that require only sensible heating
energy recovery.
4/29/20224/27/2022N/A4/29/2022
cb1.1, 2.1, 2.2, 2.3, 3.2,
4.1.1.6, 4.2.1.4, 4.1.2.5,
10.4.6, Table G3.1
Revises the 90.1 Purpose and Scope to apply to areas outside of the physical building that qualify under the new
definition for “site.”
2/2/20221/28/20222/2/20223/1/2022
ceA2.5, A3.3, A9.2, 13Adds new reference and requirements for steel-framed walls aligned with ANSI/AISI S250, which provides additional
options for wall framing and insulation placement.
4/29/20224/27/2022N/A4/29/2022
cf10.4.3, 10.9.3Introduces provisions that improve elevator fan, lighting, and movement efficiency.4/29/20224/27/2022N/A4/29/2022
cg5.5.3, A9.4.7Adds a definition for insulated metal panels (IMPs) and a new section to explain how the U-factor of a given IMP is
determined.
4/29/20224/27/2022N/A4/29/2022
ciTable 6.5.1-1Requires fan cooling-units outside of the building to have an economizer at the indicated capacity range.4/29/20224/27/2022N/A4/29/2022
cjTable 6.8.1-16Corrects numerical errors that were present in the centrifugal chiller category when it was updated in Addendum y.4/29/20224/27/2022N/A4/29/2022
cm13Updates the normative references used in the standard to the latest applicable versions.7/29/20227/26/2022N/A7/29/2022
a. These descriptions may not be complete and are provided for information only.a. These descriptions may not be complete and are provided for information only.a. These descriptions may not be complete and are provided for information only.a. These descriptions may not be complete and are provided for information only.a. These descriptions may not be complete and are provided for information only.a. These descriptions may not be complete and are provided for information only.a. These descriptions may not be complete and are provided for information only.