Light Trespass
Do not exceed the following luminaire backlight and glare ratings (based on the specific light source installed in the luminaire), as defined in IES TM-15-11, Addendum A, based on the mounting location and distance from the lighting boundary. Table 2. Maximum Backlight and Glare Ratings
| Col1 | MLO Lighting Zone | Col3 | Col4 | Col5 | Col6 |
|---|---|---|---|---|---|
| Luminaire mounting | LZ0 | LZ1 | LZ2 | LZ3 | LZ4 |
| Allowed Backlight Ratings | Allowed Backlight Ratings | Allowed Backlight Ratings | Allowed Backlight Ratings | Allowed Backlight Ratings | |
| > 2 mounting heights from lighting boundary | B1 | B3 | B4 | B5 | B5 |
| 1 to 2 mounting heights from lighting boundary and properly oriented | B1 | B2 | B3 | B4 | B4 |
| 0.5 to 1 mounting height to lighting boundary and properly oriented | B0 | B1 | B2 | B3 | B3 |
| < 0.5 mounting height to lighting boundary and properly oriented | B0 | B0 | B0 | B1 | B2 |
| Allowed Glare Ratings | Allowed Glare Ratings | Allowed Glare Ratings | Allowed Glare Ratings | Allowed Glare Ratings | |
| Building mounted > 2 mounting heights from any lighting boundary | G0 | G1 | G2 | G3 | G4 |
| Building mounted = 1–2 mounting heights from any lighting boundary | G0 | G0 | G1 | G1 | G2 |
| Building mounted = 0.5–1 mounting heights from any lighting boundary | G0 | G0 | G0 | G1 | G1 |
| Building mounted < 0.5 mounting heights from any lighting boundary | G0 | G0 | G0 | G0 | G1 |
| All other luminaires | G0 | G1 | G2 | G3 | G4 |
AND
Internally Illuminated Exterior Signage
Do not exceed the maximum luminance level of internally illuminated signage during nighttime hours according to Table 3.
Table 3. Maximum sign luminance
| MLO Lighting Zone | Signage Light Output |
|---|---|
| LZ0 | 50 cd/m2 |
LZ1 | 50 cd/m2 |
LZ2 | 100 cd/m2 |
LZ3 | 200 cd/m2 |
LZ4 | 350 cd/m2 |
U.S. Green Building Council LEED v5 Reference Guide for Building Design and Construction, November 2025 Edition 52