Minimum Equipment Water Efficiency

Newly installed appliances, equipment, and processes within the project boundary must meet the requirements listed in Tables 3 and 4. Existing appliances and equipment can be excluded.

Table 3. Standards for Appliances

ApplianceCol2RequirementCol4
Residential clothes washers
Residential clothes washers
ENERGY STAR® or performance equivalent
ENERGY STAR® or performance equivalent
Commercial clothes washers
Commercial clothes washers
ENERGY STAR® for commercial clothes washers with ≤ 8.0
cubic feet (227 liters) capacity or performance equivalent
ENERGY STAR® for commercial clothes washers with ≤ 8.0
cubic feet (227 liters) capacity or performance equivalent
Residential dishwashers (standard
and compact)
Residential dishwashers (standard
and compact)

ENERGY STAR® or performance equivalent

ENERGY STAR® or performance equivalent
Prerinse spray valves
Prerinse spray valves
≤ 1.3 gpm (4.9 lpm)
≤ 1.3 gpm (4.9 lpm)
Ice machines
Ice machines
ENERGY STAR® or performance equivalent and use either
air-cooled or closed-loop cooling, such as a chilled or
condenser water system

ENERGY STAR® or performance equivalent and use either
air-cooled or closed-loop cooling, such as a chilled or
condenser water system

Commercial kitchen equipment

Commercial kitchen equipment


Requirement (IP)
Requirement (SI)
Dishwasher
Undercounter
≤ 1.6 gal./rack
≤ 6.0 liters/rack
Dishwasher
Stationary, single
tank, door
≤ 1.4 gal./rack≤ 5.3 liters/rack
Dishwasher

Single tank,
conveyor
≤ 1.0 gal./rack
≤ 3.8 liters/rack
Dishwasher
Multiple tank,
conveyor
≤ 0.9 gal./rack≤ 3.4 liters/rack
Dishwasher
Flight machine
≤ 180 gal./hr
≤ 680 liters/hr
Food steamer
Boilerless/
connectionless
≤ 2 gal./hr/pan≤ 7.5 liters/hr/pan
Food steamer

Steam generator
≤ 5 gal./hr/pan
≤ 19 liters/hr/pan
Combination
oven
Countertop or
stand
≤ 1.5 gal./pan≤ 5.7 liters/pan
Combination
oven

Roll-in
≤ 1.5 gal./pan≤ 5.7 liters/pan

NOTE: gpm = gallons per minute; lpm = liters per minute.

Table 4. Standards for Processes

ProcessRequirement
Heat rejection and cooling
No once-through cooling with potable water for any equipment or
appliances that reject heat.
Cooling towers and
evaporative condensers
Equip with all the following:

Makeup water meters

Conductivity controllers and overflow alarms

Efficient drift eliminators that reduce drift to max of 0.001% of
recirculated water volume for counterflow towers and 0.002%
of recirculated water flow for cross-flow towers.

U.S. Green Building Council LEED v5 Reference Guide for Building Design and Construction, November 2025 Edition 57