Equipment efficiency : Determine weighted average COP using either of the following:

  • Equipment efficiencies at rated conditions : For equipment with multiple rated conditions, use the rating closest to 17°F (−9°C) outside air dry-bulb temperatures (OA db), 32°F (0°C) entering liquid temperature, or 44°F (6°C) heating source leaving liquid temperature.

  • Annual average COP calculated with an energy simulation.

District energy : Projects with district energy must comply with the requirements of this credit at the district facility or see additional guidance for interpretation of credit requirements.

Fuel cells : Fuel cells using fossil fuel are ineligible for credit.

Low temperatures : The term Low temperatures refers to OA db below 20°F (−6.5°C).

REQUIREMENTS: CORE AND SHELL

Achievement PathwaysPoints

Core and Shell

1–4

Option 1. Electrification

2–4

Path 1. No On-Site Combustion

3–4

OR



Path 2. No On-Site Combustion Except at Low Temperatures

1–3

Case 1. Space Heating

1–2

AND/OR



Case 2. Service Water Heating

1

OR



Path 3. No On-Site Combustion—Limited Scope

1–2

AND/OR



Option 2. Electrification Readiness

1

Option 1. Electrification (2–4 points)

For Paths 1 and 2:

- Include all heating and service hot water systems necessary to meet total building

heating and SWH load in the calculations of weighted average COP.

- Future heating or SWH systems must be included in the calculations with a COP of

1.0.

- Future equipment may be excluded from the calculations and deemed as compliant

when the applicable building code, or construction drawings for projects with tenancy, confirms a weighted average COP of at least 1.8 for future installed equipment.

U.S. Green Building Council LEED v5 Reference Guide for Building Design and Construction, November 2025 Edition 88