PATH 1. NO ON-SITE COMBUSTION (3–4 POINTS)

Design and operate the project from start-up with no on-site combustion except for emergency support systems.

Combined weighted average equipment efficiency for space heating and SWH must be at least 1.8 COP for 4 points and at least 1.3 COP for 3 points.

The following equipment may be excluded from the COP determination:

- Space heating equipment in climate zones 0–2.

- Supplemental heating equipment designed only for operation at low temperatures.

- SWH equipment with a total project SWH capacity less than 34,000 Btu/hr (10 kW).

- SWH equipment in nonresidential spaces complying with the point-of-use water

heater criteria in ASHRAE 90.1-2022, Section 11.5.2.3.3, W05, without exceptions.

OR

PATH 2. NO ON-SITE COMBUSTION EXCEPT AT LOW TEMPERATURES (1–3 POINTS)

Pursue any combination of the following cases for a maximum of 3 points:

Case 1. Space Heating (1–2 points)

Design space heating to be capable of operating without on-site combustion except at low temperatures. Projects must have a weighted average space heating equipment efficiency of at least 1.8 COP for 2 points and 1.3 COP for 1 point.

The following equipment may be excluded from the COP determination:

- Space heating equipment in climate zones 0–2

- Supplemental heating equipment designed only for operation at low temperatures

AND/OR

Case 2. Service Water Heating (1 point)

Design SWH systems to be capable of operating without on-site combustion except at low temperatures. Projects with total SWH capacity exceeding 34,000 Btu/hr (10 kW) must have a weighted average service hot water equipment efficiency of at least 1.8 COP or domestic hot water solar fraction of at least 0.4.