Balanced Ventilation
Design the ventilation and exhaust airflows within 10% of each other and include a testing, adjusting, and balancing (TAB) report demonstrating balanced ventilation in the commissioning scope. This requirement does not apply to Core and Shell projects.
AND
Infiltration
Use an air leakage test to demonstrate a measured air leakage of the building envelope less than or equal to Table 1. Buildings smaller than 25,000 square feet (2,322 square meters) must use a whole-building air leakage test.
- Complete air leakage testing using ASTM _E779_, _ANSI/RESNET/ICC 380_, _ASTM_
E3158, ASTM E1827, or equivalent.
- For buildings greater than 5,000 sq. ft. (465 sq. m.), maximum air leakage is
determined per square feet or square meter of building envelope area (including exterior walls, roofs, and base floor/slab).
- For projects that include both new construction and major renovation, use the
weighted average maximum air leakage.
Table 1. Caps on Air Leakage Rates
| Building Conditioned Floor Area (CFA) | Pressure Test Conditions Across the Building Envelope | Maximum Air Leakage1 | Col4 |
|---|---|---|---|
| Building Conditioned Floor Area (CFA) | Pressure Test Conditions Across the Building Envelope | New Construction | Major Renovation |
≥ 5,000 sq. ft. (465 sq. m.) | At pressure difference of 50 pascals (0.2 in H2O) | 0.13 cfm/sq. ft. (0.65 L/s/m2) | 0.20 cfm/sq. ft. (1.0 L/s/m2) |
≥ 5,000 sq. ft. (465 sq. m.) | At pressure difference of 75 pascals (0.3 in H2O) | 0.18 cfm/sq. ft. (0.90 L/s/m2) | 0.27 cfm/sq. ft. (1.35 L/s/m2) |
< 5,000 sq. ft. (465 sq. m.) | At 50 pascals (0.2 in in H2O) | 1 ACH | 1.5 ACH |
< 5,000 sq. ft. (465 sq. m.) | At 75 pascals (0.3 in H2O) | 1.35 ACH | 2 ACH |
OR
Residential (2 points)
Balanced Ventilation. Meet the New Construction requirements.
AND
INFILTRATION
U.S. Green Building Council LEED v5 Reference Guide for Building Design and Construction, November 2025 Edition 93