LEED v5 BD+C Rating System_November 2025_clean - Page 111
Extracted Content
Case 2. ASHRAE 90.1-2022 (2–6 points)
-
Comply with the provisions of ASHRAE 90.1-2022, Sections 5–11.
-
Implement incremental ASHRAE 90.1 2022, Section 11 credits above the minimum required from the list of eligible measures below.
o Central systems: 1 point for every 13 incremental energy credits where the LEED
BD+C: Core and Shell project includes a central HVAC system or service water heating system that includes chillers, boilers, service water heating equipment, or loop pumping systems with heat rejection.
o All others: 1 point for every nine incremental energy credits for all other LEED
BD+C: Core and Shell projects.
Eligible measures from ASHRAE 90.1-2022, Section 11.5.2, for LEED points
-
HVAC measures (H01 to H07)
-
Service water heating measures (W01 to W09)
-
Lighting measures (L01 to L06)
-
G07 building mass/night flush
Table 6. Points for ASHRAE 90.1-2022, Section 11 Credits
| Points | Compliance Path | Col3 | Col4 | Col5 |
|---|---|---|---|---|
| Points | Case 1.****ASHRAE **90.1-2019 ** | Case 1.****ASHRAE **90.1-2019 ** | **Case 2.****ASHRAE 90.1-2022 ** | **Case 2.****ASHRAE 90.1-2022 ** |
| Points | Central Systems | All Others | Central Systems | All Others |
| 1 | 13 credits | 9 credits | N/A | N/A |
2 | 26 credits | 18 credits | Min. required by_ASHRAE_ 90.1-2022 | Min. required by_ASHRAE_ 90.1-2022 |
| 3 | 39 credits | 27 credits | Min. required + 13 credits | Min. required + 9 credits |
4 | 52 credits | 36 credits | Min. required + 26 credits | Min. required + 18 credits |
5 | 65 credits | 45 credits | Min. required + 39 credits | Min. required + 27 credits |
6 | – | – | Min. required + 52 credits | Min. required + 36 credits |
AND/OR
PATH 2. PLUG AND PROCESS LOADS (1–3 POINTS)
Case 1. Plug Load Management (1 point)
Implement the following:
- Provide to all regular occupants of the building a plug load dashboard accessed through an application that displays base building plug loads and allows tenants to choose whether to display plug loads to their occupants.
U.S. Green Building Council LEED v5 Reference Guide for Building Design and Construction, November 2025 Edition 104