Residential

  • Meet the preceding requirements for all areas inside and outside the building except dwelling units and private balconies.

    • For residential projects that do not prohibit smoking, each dwelling unit where smoking will be permitted must meet the following compartmentalization requirements:

o Perform a blower door test of residential dwelling units, following the procedures in

ANSI/RESNET/ICC 380 or equivalent. For each unit tested, demonstrate a maximum leakage of enclosure area that is no more than 1.5 times the thresholds identified in Table 1 (“enclosure area” refers to all surfaces enclosing the dwelling unit, including exterior and party walls, floors, and ceilings). Demonstrate a weighted average leakage of enclosure area for the building, including dwelling units, that complies with the caps in the limits identified in Table 1.

Table 1. Caps on Air Leakage Rates

Building
Conditioned
Floor Area (CFA)
Pressure Test
Conditions Across the
Building Envelope
Maximum Air LeakageCol4
Building
Conditioned
Floor Area (CFA)
Pressure Test
Conditions Across the
Building Envelope
New Construction
Major Renovation

≥ 5,000 sq. ft.
(465 sq. m.)


At pressure difference of
50 pascals (0.2 in H2O)
0.13 cfm/sq. ft.
(0.65 L/s*sq. m.)
0.20 cfm/sq. ft.
(1.0 L/s*sq. m.)

≥ 5,000 sq. ft.
(465 sq. m.)

At pressure difference of
75 pascals (0.3 in H2O)
0.18 cfm/sq. ft.
(0.90 L/s*sq. m.)
0.27 cfm/sq. ft.
(1.35 L/s*sq. m.)
< 5,000 sq. ft.
(465 sq. m.)

At 50 pascals
(0.2 in H2O)

1 ACH

1.5 ACH



At 75 pascals (0.3 in
H2O)
1.35 ACH
2 ACH