LEED v5 BD+C Rating System_November 2025_clean - Page 162

Extracted Content

Indoor Environmental Quality Credit

ENHANCED AIR QUALITY

EQc1 New Construction (1 point) Core and Shell (1 point)

INTENT

To design for increased indoor air quality (IAQ) to better protect the health of building occupants.

REQUIREMENTS

Achievement PathwaysPoints

New Construction and Core and Shell

1

Option 1. Increased Ventilation

1

OR



Option 2. Enhanced Indoor Air Quality Design

1

Design the building to exceed the requirements of ASHRAE 62.1-2022, Section 6. If using the VRP to comply with EQp2: Fundamental Air Quality, use Option 1 or Option 2; if using the IAQP, use Option 2.

Option 1. Increased Ventilation (1 point)

Increase breathing zone outdoor air ventilation rates by at least 15% above the minimum rates (for 1 point, or 30% for exemplary performance) as determined in EQp2: Fundamental Air Quality .

Increased outdoor air rates should be provided to 95% of all regularly occupied spaces.

OR

Option 2. Enhanced Indoor Air Quality Design (1 point)

In addition to the design compounds and design limits outlined in ASHRAE 62.1-2022, Tables 65 and 6-6, design and verify enhanced IAQ using the lower design limits listed below in Table 1.

U.S. Green Building Council LEED v5 Reference Guide for Building Design and Construction, November 2025 Edition 155